ToolBelt HQ

Conduit Fill: 4 #12 THHN in 3/4" EMT

Two-circuit or four-wire configuration commonly used in commercial wiring.

Results

Fill Percentage10%
Max Allowed40%
StatusPASS
Conductor Area0.0532sq in
Conduit Area0.533sq in

Need to adjust these values? Use the full calculator: