What Size Wire for a 100 Amp 240V Circuit with 6 Conductors?

Sub-panel feeders with multiple circuits in one conduit require careful derating calculations. This scenario accounts for bundling 6 current-carrying conductors.

Results

Minimum Wire Size1 AWG
Base Ampacity130A
Adjusted Ampacity108.2A
Temp Correction Factor1.04
Bundling Factor0.8