Understanding Voltage Drop: When Wire Length Matters

Why voltage drop matters for long circuit runs, the NEC 3% and 5% recommendations, and how to calculate and fix excessive voltage drop.

Understanding Voltage Drop: When Wire Length Matters

When electricity travels through wire, resistance causes voltage loss between the source and the load. This phenomenon, known as voltage drop, is one of the most misunderstood issues in electrical installations. While often overlooked during installation, excessive voltage drop leads to equipment malfunction, premature failure, energy waste, and code compliance issues that result in costly callbacks.

Understanding when voltage drop matters and how to calculate it properly separates professional installations from amateur work. This guide covers everything you need to know about voltage drop calculations, NEC recommendations, real-world effects on equipment, and proven solutions for long circuit runs.

The Physics Behind Voltage Drop

Voltage drop occurs due to the resistance inherent in all conductors. As current flows through wire, this resistance converts electrical energy into heat, reducing the voltage available at the load end of the circuit. The longer the wire run and the higher the current, the greater the voltage loss.

Think of it like water pressure in a long hose. The longer the hose and the more water flowing through it, the lower the pressure at the end. Similarly, electrical circuits experience voltage loss over distance, particularly under heavy load.

This isn't just a theoretical concern. A motor rated for 240 volts that receives only 228 volts (5% drop) will draw more current to produce the same power output, running hotter and wearing out faster. LED fixtures on circuits with excessive drop may flicker or fail to reach full brightness. Heating elements produce less heat. Compressors may fail to start entirely.

The Voltage Drop Formula Explained

For single-phase circuits, the standard voltage drop calculation uses this formula:

Vd = (2 × K × I × D) / CM

Let's break down each variable:

K (resistivity constant): This value represents the specific resistance of the conductor material in ohms per circular mil-foot:

  • 12.9 for copper at 75°C (the most common conductor material)
  • 21.2 for aluminum at 75°C

I (current in amperes): The actual current the circuit will carry, not the breaker size. For continuous loads, use 125% of the actual load per NEC requirements.

D (one-way distance in feet): The physical distance from the power source to the load, measured along the wire route. Do not double this distance; the formula's "2" factor accounts for the round trip.

CM (circular mils): The cross-sectional area of the conductor. This is found in NEC Table 8:

  • 14 AWG = 4,110 CM
  • 12 AWG = 6,530 CM
  • 10 AWG = 10,380 CM
  • 8 AWG = 16,510 CM
  • 6 AWG = 26,240 CM
  • 4 AWG = 41,740 CM
  • 3 AWG = 52,620 CM
  • 2 AWG = 66,360 CM
  • 1 AWG = 83,690 CM
  • 1/0 AWG = 105,600 CM
  • 2/0 AWG = 133,100 CM
  • 3/0 AWG = 167,800 CM
  • 4/0 AWG = 211,600 CM

The "2" multiplier: This accounts for current traveling down one conductor and returning on the other (completing the circuit). Both conductors contribute to total resistance.

Three-Phase Voltage Drop Formula

For three-phase circuits, the formula changes slightly:

Vd = (1.732 × K × I × D) / CM

The factor 1.732 (square root of 3) replaces the "2" because three-phase systems distribute current across three conductors more efficiently than single-phase systems. Three-phase voltage drop is inherently lower for the same power delivery.

Temperature Correction

The K values listed above assume conductors operating at 75°C. For different temperatures or more precise calculations, NEC Table 8 provides DC resistance values per 1,000 feet at 75°C. For AC circuits, you must also consider reactance (Table 9), though resistance is the dominant factor in most residential and light commercial installations.

In extremely hot environments (attics exceeding 120°F, outdoor conduit in desert climates), conductor resistance increases, leading to greater voltage drop than calculated using standard K values. For critical applications in high-temperature environments, consult NEC Chapter 9, Table 8 and apply temperature correction factors.

NEC Voltage Drop Recommendations

The National Electrical Code addresses voltage drop in NEC 210.19(A) Informational Note No. 4 for branch circuits and NEC 215.2(A)(1) Informational Note No. 2 for feeders:

  • 3% maximum recommended drop for branch circuits (final circuits to outlets/equipment)
  • 5% maximum recommended total drop for combined feeder and branch circuits from service entrance to the furthest outlet

These are recommendations, not mandatory requirements. The NEC uses "Informational Note" language, meaning these are best practices for performance and efficiency rather than code minimums you must meet to pass inspection.

However, these recommendations exist for critical reasons:

Equipment Performance: Most electrical equipment is designed to operate within ±10% of its rated voltage. A 5% voltage drop plus normal utility voltage variation (which can be -5% during peak demand) puts you at the edge of acceptable operating range.

Motor Protection: Motors are particularly sensitive to low voltage. A motor operating at 10% below nameplate voltage draws significantly more current, overheats, and experiences reduced lifespan. Excessive voltage drop can prevent motors from starting under load.

Energy Efficiency: Voltage drop represents wasted energy converted to heat in the conductors. This waste occurs continuously whenever the circuit is energized, costing money over the life of the installation.

Code Compliance Intent: While not enforced as hard requirements, inspectors in some jurisdictions may flag excessive voltage drop as a workmanship issue, especially on critical circuits like fire pumps, emergency systems, or service feeders.

What 3% and 5% Mean in Real Voltage

For practical application, here's what these percentages mean:

120V circuits:

  • 3% drop = 3.6 volts (116.4V delivered)
  • 5% drop = 6.0 volts (114.0V delivered)

240V circuits:

  • 3% drop = 7.2 volts (232.8V delivered)
  • 5% drop = 12.0 volts (228.0V delivered)

208V three-phase circuits:

  • 3% drop = 6.24 volts (201.76V delivered)
  • 5% drop = 10.4 volts (197.6V delivered)

480V three-phase circuits:

  • 3% drop = 14.4 volts (465.6V delivered)
  • 5% drop = 24.0 volts (456.0V delivered)

Real-World Effects of Excessive Voltage Drop

Voltage drop isn't just a number on a calculation. It has tangible, measurable effects on electrical equipment:

Motors and Compressors

Motors are the most vulnerable loads. A motor running at 10% below rated voltage will:

  • Draw 11% more current
  • Produce 19% less starting torque
  • Generate significantly more heat
  • Experience reduced lifespan from thermal stress

HVAC compressors, well pumps, and shop equipment may fail to start if voltage sags below 90% of nameplate rating. Once running, they operate inefficiently and overheat.

LED Lighting

LEDs are sensitive to both high and low voltage:

  • Dimming or reduced light output with low voltage
  • Flickering, especially with incompatible dimmers
  • Driver failure from operating outside design range
  • Color temperature shifts in some fixtures

Heating Elements

Resistive heating elements (water heaters, baseboard heaters, space heaters) follow the power formula P = V²/R. A 5% voltage drop results in approximately 10% less heat output. A water heater on an undervolted circuit takes longer to recover and may never reach target temperature under continuous demand.

Electronics and Appliances

Modern appliances with electronic controls may:

  • Display error codes and shut down
  • Experience reduced performance
  • Suffer shortened component lifespan
  • Trip overcurrent protection due to compensatory current draw

Refrigerators, freezers, and other compressor-based appliances are particularly sensitive, as they combine motor loads with electronic controls.

Battery Chargers

Electric vehicle chargers, tool battery chargers, and battery backup systems may reduce charging rate or fail to charge entirely when input voltage is too low. Some chargers have undervoltage lockout circuits that prevent operation below threshold.

Voltage Drop Calculation Examples

Let's work through real-world examples across different scenarios:

Example 1: Detached Garage Circuit (Short Run)

Scenario: 100-foot run to detached garage, 20-amp circuit, 12 AWG copper wire, 120V

  • K = 12.9 (copper)
  • I = 20 amps
  • D = 100 feet
  • CM = 6,530 (12 AWG from Table 8)

Vd = (2 × 12.9 × 20 × 100) / 6,530 = 51,600 / 6,530 = 7.9 volts

Percentage drop = 7.9 / 120 = 6.6%

Result: This exceeds the 3% recommendation and is unacceptable. The circuit requires upsizing to 10 AWG.

With 10 AWG (10,380 CM): Vd = 51,600 / 10,380 = 4.97 volts = 4.1% drop

Still over 3%, but acceptable for many applications. For critical loads, consider 8 AWG.

Example 2: Well Pump (Long Run, 240V)

Scenario: 250-foot run to well pump, 240V, 20-amp continuous load, evaluating wire sizes

At 10 AWG: Vd = (2 × 12.9 × 20 × 250) / 10,380 = 12.4 volts = 5.2% drop

At 8 AWG: Vd = (2 × 12.9 × 20 × 250) / 16,510 = 7.8 volts = 3.25% drop

At 6 AWG: Vd = (2 × 12.9 × 20 × 250) / 26,240 = 4.9 volts = 2.0% drop

Result: 8 AWG meets the 3% recommendation. 6 AWG provides better performance and should be considered for submersible pumps, which are sensitive to voltage and expensive to replace.

Example 3: Sub-Panel Feeder

Scenario: 150-foot feeder to sub-panel, 100-amp load, 240V, aluminum conductors

For 100 amps continuous, NEC requires 125% = 125 amps for conductor sizing. However, for voltage drop calculation, use actual load (100 amps).

With 1/0 aluminum (105,600 CM):

  • K = 21.2 (aluminum)
  • I = 100 amps
  • D = 150 feet
  • CM = 105,600

Vd = (2 × 21.2 × 100 × 150) / 105,600 = 636,000 / 105,600 = 6.0 volts = 2.5% drop

Result: This meets the 3% feeder recommendation and leaves 2.5% headroom for branch circuit drop (to stay within combined 5% total).

Example 4: RV Hookup (50-Amp, 120/240V)

Scenario: 80-foot run to RV pedestal, 50-amp service, 120/240V

Use worst case: 50 amps at 120V (single phase to neutral).

With 6 AWG copper (26,240 CM): Vd = (2 × 12.9 × 50 × 80) / 26,240 = 3.9 volts = 3.3% drop at 120V

With 4 AWG copper (41,740 CM): Vd = (2 × 12.9 × 50 × 80) / 41,740 = 2.5 volts = 2.1% drop at 120V

Result: 6 AWG exceeds 3%. Use 4 AWG for 50-amp RV circuits.

Comparison Table: 20-Amp Circuit at 120V

| Wire Size | 50 ft | 100 ft | 150 ft | 200 ft | 250 ft | |-----------|-------|--------|--------|--------|--------| | 14 AWG | 3.1% | 6.3% | 9.4% | 12.5% | 15.6% | | 12 AWG | 2.0% | 3.9% | 5.9% | 7.9% | 9.8% | | 10 AWG | 1.2% | 2.5% | 3.7% | 5.0% | 6.2% | | 8 AWG | 0.8% | 1.6% | 2.3% | 3.1% | 3.9% |

This table clearly shows why 14 AWG is unsuitable for runs over 50 feet at 20 amps, and why 12 AWG struggles beyond 75 feet.

Strategies to Reduce Voltage Drop

When calculations show excessive voltage drop, you have several proven solutions:

1. Upsize the Conductor

The most direct solution is increasing wire size. Each three-gauge increase (12 AWG → 10 AWG → 8 AWG) reduces voltage drop by approximately 37%.

Cost vs. Benefit: Larger wire costs more initially, but eliminates energy waste and equipment problems for the life of the installation. For permanent installations over 100 feet, oversizing by one gauge is cheap insurance.

Ampacity vs. Voltage Drop: Wire may be adequately sized for ampacity (current-carrying capacity per NEC Table 310.16) but still have excessive voltage drop. Always check both. Voltage drop often governs on long runs, requiring larger wire than ampacity alone would dictate.

2. Use 240V Instead of 120V

Where equipment can operate on either voltage, choose 240V. For the same power delivery, 240V circuits carry half the current, which cuts voltage drop in half.

A 20-amp 120V circuit (2,400 watts) has the same power delivery as a 10-amp 240V circuit. The voltage drop on the 240V circuit will be half as much, and when expressed as a percentage of the higher voltage, the effect is even more dramatic.

Example: A 3.8-volt drop represents 3.2% of 120V but only 1.6% of 240V.

This is why electric water heaters, dryers, ranges, and workshop equipment use 240V: efficiency over long runs.

3. Install a Sub-Panel Closer to the Load

For multiple circuits serving a distant area (barn, shop, detached garage), running a larger feeder to a sub-panel is more economical than running multiple oversized branch circuits.

A single 100-amp feeder can supply numerous branch circuits with minimal voltage drop on the feeder, and short branch circuits from the sub-panel keep total drop within limits.

Design Approach:

  • Size feeder for 3% maximum drop
  • Keep branch circuits from sub-panel under 50 feet where possible
  • This keeps combined feeder + branch drop under 5%

4. Reduce the Load

Sometimes the solution is reducing current rather than increasing wire size:

  • Split one large circuit into two smaller ones
  • Eliminate unnecessary loads
  • Use more efficient equipment (LED vs. incandescent, high-efficiency motors)

5. Use Aluminum Conductors (for Large Feeders)

For large feeders (100+ amps), aluminum offers significant cost savings. While aluminum has higher resistance than copper (K = 21.2 vs. 12.9), you can upsize aluminum to match copper's voltage drop performance at lower total cost.

Cost-Benefit Example: 150-foot feeder, 100 amps, 240V

  • Copper 1/0 AWG: ~$500 material cost, 2.5% drop
  • Aluminum 2/0 AWG: ~$200 material cost, 2.8% drop

The aluminum option costs 60% less with minimal performance difference. For long service laterals and feeders, aluminum is industry standard.

Important: Use anti-oxidant compound, torque lugs properly, and ensure terminations are rated for aluminum (AL or CU/AL marking).

6. Consider Parallel Conductors

For very large loads, NEC allows parallel conductors (multiple wires per phase). Two 3/0 copper conductors in parallel have double the circular mils of a single 3/0, halving the voltage drop.

Paralleling requires:

  • All conductors the same length
  • All conductors the same material and size
  • Conductors 1/0 AWG or larger
  • Proper load sharing between parallel sets

This is common in commercial/industrial services but rarely needed in residential applications.

Common Scenarios and Recommended Wire Sizes

Detached Garage (120V, 20A)

| Distance | Minimum Wire Size | |-----------|-------------------| | Up to 64 ft | 12 AWG | | 65-100 ft | 10 AWG | | 101-160 ft | 8 AWG | | 161-255 ft | 6 AWG |

Well Pump (240V, 20A Continuous)

| Distance | Minimum Wire Size | |-----------|-------------------| | Up to 128 ft | 12 AWG | | 129-200 ft | 10 AWG | | 201-320 ft | 8 AWG | | 321-510 ft | 6 AWG |

Barn/Shop Sub-Panel (240V, 100A)

| Distance | Minimum Wire Size (Copper) | Minimum Wire Size (Aluminum) | |----------|----------------------------|------------------------------| | Up to 100 ft | 1 AWG | 1/0 AWG | | 101-150 ft | 1/0 AWG | 2/0 AWG | | 151-200 ft | 2/0 AWG | 3/0 AWG | | 201-250 ft | 3/0 AWG | 4/0 AWG |

EV Charger (240V, 40A Continuous)

| Distance | Minimum Wire Size | |----------|-------------------| | Up to 80 ft | 8 AWG | | 81-128 ft | 6 AWG | | 129-200 ft | 4 AWG | | 201-320 ft | 2 AWG |

Interaction with NEC Ampacity Requirements

Voltage drop calculations are separate from but related to ampacity requirements. You must satisfy both:

Ampacity (NEC 310.16): Ensures wire doesn't overheat under load. Based on conductor size, insulation type, ambient temperature, and number of current-carrying conductors.

Voltage Drop: Ensures adequate voltage reaches the load. Based on conductor size, current, and distance.

For short runs, ampacity governs. For long runs, voltage drop governs.

Example: A 20-amp circuit requires 12 AWG minimum (ampacity). But for a 200-foot run, voltage drop requires 8 AWG. You must use 8 AWG to satisfy both requirements.

Always calculate both and use whichever requires larger wire.

Temperature Correction and Conduit Fill

When conductors operate above 30°C (86°F) ambient temperature, ampacity must be derated per NEC 310.15(B)(2)(a). Common derating scenarios:

  • Attics in summer: 50°C (122°F) or higher
  • Outdoor conduit in direct sun: 40-50°C
  • Rooftops: 35-45°C

Temperature correction factors reduce allowable ampacity but don't directly change voltage drop calculations (though higher temperature does slightly increase resistance).

Conduit fill (NEC Chapter 9, Table 1) limits the number of conductors in a raceway. More than three current-carrying conductors require ampacity derating per NEC 310.15(B)(3)(a).

These factors can force you to upsize wire for ampacity, which has the beneficial side effect of reducing voltage drop.

Special Considerations for Three-Phase Systems

Three-phase systems are more efficient for power delivery:

  • Lower voltage drop for equivalent power (factor of 1.732 instead of 2)
  • Smaller conductors for the same kW delivery
  • More stable voltage for motor loads

For large commercial/industrial installations or farms with three-phase service, always run three-phase to motor loads rather than converting to single-phase.

Testing and Verification

After installation, verify voltage drop with measurements:

  1. Measure voltage at the panel with load OFF
  2. Measure voltage at the load end with load ON (full load)
  3. Subtract: voltage drop = V(panel) - V(load)
  4. Calculate percentage: (voltage drop / source voltage) × 100

If measured drop exceeds calculations, investigate:

  • Poor connections (high resistance at terminals)
  • Damaged conductors
  • Undersized neutral (causes voltage drop on 120V loads in 120/240V systems)
  • Incorrect wire size (wrong AWG installed)

Voltage Drop in Temporary Power

Job site temporary power is notorious for voltage drop issues:

  • Long extension cord runs
  • Undersized cords (16 AWG, 14 AWG)
  • Multiple cords in series
  • Poor connections

A 100-foot 12 AWG extension cord carrying 15 amps has about 3.6V drop (3% at 120V). Add a second 100-foot cord in series and you're at 7.2V drop (6%), which prevents many tools from starting.

Best Practices for Temporary Power:

  • Use 10 AWG or larger for runs over 50 feet
  • Minimize cord length and number of connections
  • Plug heavy loads (table saws, compressors, welders) directly into generator or panel
  • Use 240V for high-power tools where available

Common Mistakes to Avoid

  1. Using breaker size instead of actual load: A 20-amp breaker doesn't mean 20 amps flows continuously. Calculate based on actual connected load.

  2. Forgetting continuous load factor: Motors and other continuous loads require 125% multiplier for conductor sizing (NEC), though voltage drop calculations use actual running current.

  3. Doubling the distance incorrectly: The formula already includes the factor of 2 for round-trip. Don't enter 200 feet if the one-way distance is 100 feet.

  4. Ignoring voltage drop on neutrals: In multiwire branch circuits or systems with unbalanced loads, neutral voltage drop matters. Undersized neutrals cause voltage issues on 120V loads.

  5. Mixing copper and aluminum values: Using K=12.9 with aluminum conductors gives false results. Verify the K constant matches your conductor material.

  6. Not accounting for temperature: In extreme heat environments, conductor resistance increases. Standard calculations assume 75°C conductor temperature.

  7. Ignoring the effect on motors: Even if voltage drop meets 3% recommendation, motors near the limit may have starting problems. For critical motor loads, aim for 2% or less.

Practical Takeaways

  • Always calculate voltage drop for runs over 50 feet or loads over 15 amps
  • The NEC 3% and 5% recommendations exist for performance reasons, not just code compliance
  • Voltage drop and ampacity are separate requirements; satisfy both
  • When in doubt, upsize the wire one gauge; the cost difference is minimal compared to callbacks
  • Use 240V instead of 120V wherever possible for long runs
  • Sub-panels are economical for serving multiple distant loads
  • Aluminum feeders save significant money on large, long runs
  • Test installed circuits under load to verify voltage delivery

Proper voltage drop planning prevents equipment damage, improves energy efficiency, and ensures installations that perform reliably for decades. Use a voltage drop calculator to quickly evaluate scenarios, but understand the underlying principles so you can make informed decisions when field conditions demand creative solutions. The few extra dollars spent on appropriately sized conductors pay dividends every day the circuit operates.