ToolBelt HQ

Conduit Fill: Mixed 2 #10 + 3 #12 THHN in 1" EMT

Multiple circuits with different wire sizes sharing common conduit run.

Results

Fill Percentage9.5%
Max Allowed40%
StatusPASS
Conductor Area0.0821sq in
Conduit Area0.864sq in

Need to adjust these values? Use the full calculator:

Open Full Calculator